Digital control of a three-phase grid connected inverter
Digital control of a three-phase grid connected inverter
This paper presents the design and practical implementation of a digital current controller for a three-phase PWM voltage source inverter connected to the grid via an LCL filter to produce a high quality current injected into the grid. A two feedback loops control system is proposed, with an outer grid current loop and an inner filter capacitor current loop. The controller also incorporates a grid voltage feedforward loop to compensate for the effect of the utility voltage disturbance. The paper also discusses the effect of the sampling and computational time delay both on system stability and current quality. This time delay is shown to reduce the stability of the inner loop. However, it is also shown that it is better, from the point of view of output current THD quality, to increase the inner loop time delay to a full one sampling period, so that the mains frequency envelope (nearly ripple free) current component is sampled at the peaks and troughs of the PWM, away from the switching instances (and associated noise) of the transistors. To ensure system stability, a capacitor current observer is proposed to compensate for the computational time delay. The design of the capacitor current observer and the controller are discussed. Simulation and practical results are presented to validate the design.
grid-connected inverters, PWM, DSP
Abu-Sara, Mohammad
cde8e173-f938-4210-8b9d-d1bf3a9a429a
Sharkh, Suleiman
c8445516-dafe-41c2-b7e8-c21e295e56b9
Abu-Sara, Mohammad
cde8e173-f938-4210-8b9d-d1bf3a9a429a
Sharkh, Suleiman
c8445516-dafe-41c2-b7e8-c21e295e56b9
Abu-Sara, Mohammad and Sharkh, Suleiman
(2010)
Digital control of a three-phase grid connected inverter.
International Journal of Power Electronics.
(In Press)
Abstract
This paper presents the design and practical implementation of a digital current controller for a three-phase PWM voltage source inverter connected to the grid via an LCL filter to produce a high quality current injected into the grid. A two feedback loops control system is proposed, with an outer grid current loop and an inner filter capacitor current loop. The controller also incorporates a grid voltage feedforward loop to compensate for the effect of the utility voltage disturbance. The paper also discusses the effect of the sampling and computational time delay both on system stability and current quality. This time delay is shown to reduce the stability of the inner loop. However, it is also shown that it is better, from the point of view of output current THD quality, to increase the inner loop time delay to a full one sampling period, so that the mains frequency envelope (nearly ripple free) current component is sampled at the peaks and troughs of the PWM, away from the switching instances (and associated noise) of the transistors. To ensure system stability, a capacitor current observer is proposed to compensate for the computational time delay. The design of the capacitor current observer and the controller are discussed. Simulation and practical results are presented to validate the design.
Text
AuthorFinalVersion.pdf
- Author's Original
Restricted to Repository staff only
Request a copy
More information
Accepted/In Press date: 2010
Keywords:
grid-connected inverters, PWM, DSP
Identifiers
Local EPrints ID: 155155
URI: http://eprints.soton.ac.uk/id/eprint/155155
ISSN: 1756-638X
PURE UUID: 76affaea-bf79-42f0-a213-a18e65153710
Catalogue record
Date deposited: 28 May 2010 10:50
Last modified: 14 Mar 2024 02:38
Export record
Contributors
Author:
Mohammad Abu-Sara
Download statistics
Downloads from ePrints over the past year. Other digital versions may also be available to download e.g. from the publisher's website.
View more statistics