Fu, M, Chen, G, Xue, C, Ling, M and Wang, N (2003) Furfural analysis for assessing overheating in 500kV shunt reactors. At The 2nd International Conference on Insulation Condition Monitoring of Electrical Plant, Chongqing, China, 27 - 30 Oct 2003. Sichun Publishing House of Science & Technology, 72-75.

Download

Full text not available from this repository.

Description/Abstract

The furfural concentration in 500kV shunt reactor oil has been investigated to assess the overheating problems that are regarded as one of the most common defects. The research indicates that the average ageing rate of the whole oil impregnated paper insulation in shunt reactor does not exceed that in power transformers. As a result, the conclusion can be deducted that major heating spots in shunt reactors do not involve the paper insulation in the winding instead they are most likely on the metal elements due to eddy current loss.

Item Type: Conference or Workshop Item (Speech)
Additional Information: Event Dates: October 27-30, 2003
ISBNs: 7900371567
Keywords: Overheating, Paper Insulation, Furfural, Degradation, Reactor
Divisions: Faculty of Physical and Applied Science > Electronics and Computer Science
Faculty of Physical and Applied Science > Electronics and Computer Science > EEE
Item ID: 258514
Date Deposited: 10 Nov 2003
Last Modified: 02 Mar 2012 14:03
Contributors: Fu, M (Author)
Chen, G (Author)
Xue, C (Author)
Ling, M (Author)
Wang, N (Author)
Date: 2003
Additional Information: Event Dates: October 27-30, 2003
Status: Published
Publisher: Sichun Publishing House of Science & Technology
Further Information:Google Scholar
URI: http://eprints.soton.ac.uk/id/eprint/258514

Actions (login required)

View Item View Item