The energetics of gas flow and contact erosion during short circuit arcing
The energetics of gas flow and contact erosion during short circuit arcing
The processes governing the movement of short circuit arcs in circuit breakers are complex and variable and the detailed understanding of these processes is incomplete. This paper presents a new approach to our understanding of the short circuit arcing process by concentrating on the bulk thermal behavior and energetics of the arcing and gas flow during contact opening. It is shown how considerations of the arc power and the heating and vaporization of the contact material can be used to examine the flow of gas through the arc chamber and the erosion of contact material. Experimental data from a flexible test apparatus and arc imaging system along with measurements of pressure and arc current and voltage are used as the basis of the analysis. It is demonstrated how the air initially present in the arc chamber will be rapidly expelled from the arc chamber to leave an arc burning in the products of contact volatilization. Data on mass and volume flow rates are presented as well as estimates of the gas velocity in the contact region. These data provide information on the nature of the gas flow in the arc chamber as well as contact erosion during the arcing process. Arcing conditions of interest are short circuit faults (103-104 A) in low voltage (220-380 VAC) circuit breakers.
51-56
Weaver, P.M.
649cbff1-3909-4d09-bab6-79ef325089d0
Pechrach, K.
58bf3627-cfd9-4909-a76b-d236bfdcadca
McBride, J.W.
d9429c29-9361-4747-9ba3-376297cb8770
March 2004
Weaver, P.M.
649cbff1-3909-4d09-bab6-79ef325089d0
Pechrach, K.
58bf3627-cfd9-4909-a76b-d236bfdcadca
McBride, J.W.
d9429c29-9361-4747-9ba3-376297cb8770
Weaver, P.M., Pechrach, K. and McBride, J.W.
(2004)
The energetics of gas flow and contact erosion during short circuit arcing.
IEEE Transactions on Components and Packaging Technologies, 27 (1), .
(doi:10.1109/TCAPT.2004.825787).
Abstract
The processes governing the movement of short circuit arcs in circuit breakers are complex and variable and the detailed understanding of these processes is incomplete. This paper presents a new approach to our understanding of the short circuit arcing process by concentrating on the bulk thermal behavior and energetics of the arcing and gas flow during contact opening. It is shown how considerations of the arc power and the heating and vaporization of the contact material can be used to examine the flow of gas through the arc chamber and the erosion of contact material. Experimental data from a flexible test apparatus and arc imaging system along with measurements of pressure and arc current and voltage are used as the basis of the analysis. It is demonstrated how the air initially present in the arc chamber will be rapidly expelled from the arc chamber to leave an arc burning in the products of contact volatilization. Data on mass and volume flow rates are presented as well as estimates of the gas velocity in the contact region. These data provide information on the nature of the gas flow in the arc chamber as well as contact erosion during the arcing process. Arcing conditions of interest are short circuit faults (103-104 A) in low voltage (220-380 VAC) circuit breakers.
Text
22755.pdf
- Version of Record
More information
Published date: March 2004
Identifiers
Local EPrints ID: 22755
URI: http://eprints.soton.ac.uk/id/eprint/22755
ISSN: 1521-3331
PURE UUID: 71e5db42-ac92-48aa-9056-be57ffdeee09
Catalogue record
Date deposited: 15 Mar 2006
Last modified: 16 Mar 2024 02:37
Export record
Altmetrics
Contributors
Author:
P.M. Weaver
Author:
K. Pechrach
Download statistics
Downloads from ePrints over the past year. Other digital versions may also be available to download e.g. from the publisher's website.
View more statistics