A parameter for partial discharge (PD) source location within a joint bay of a three phase cross-bonded high voltage cable circuit has been assessed. Locally placed sensors can detect PD pulses that propagate within the fault related phase. However, when a cable joint bay is cross-bonded then PD signals from one phase may be measured by sensors on the other two phases as well. Current research at Southampton is considering the practical application of on-line PD monitoring techniques to three phase high voltage cable joints. A simple model, using 66kV cable sections to represent a cross-bonded circuit has been implemented. The model uses one capacitive coupler per phase. Measurement data was obtained by injecting pulses into the core conductor. Data was analysed using a clustering technique in order to determine the PD source location.
1-4244-0750-8
577-580
Hao, L
e6006548-3fc1-4a7e-9df4-a4e9a9a05c45
Lewin, P L
78b4fc49-1cb3-4db9-ba90-3ae70c0f639e
Dodd, S J
13f7eab0-eb74-4e89-83c6-555480aba185
Hao, L
e6006548-3fc1-4a7e-9df4-a4e9a9a05c45
Lewin, P L
78b4fc49-1cb3-4db9-ba90-3ae70c0f639e
Dodd, S J
13f7eab0-eb74-4e89-83c6-555480aba185

Hao, L, Lewin, P L and Dodd, S J (2007) Partial Discharge Source Characterization within a HV Cable Joint. 9th IEEE International Conference on Solid Dielectrics, Winchester, Winchester, United Kingdom. 08 - 13 Jul 2007. pp. 577-580 .

Record type: Conference or Workshop Item (Paper)

Abstract

A parameter for partial discharge (PD) source location within a joint bay of a three phase cross-bonded high voltage cable circuit has been assessed. Locally placed sensors can detect PD pulses that propagate within the fault related phase. However, when a cable joint bay is cross-bonded then PD signals from one phase may be measured by sensors on the other two phases as well. Current research at Southampton is considering the practical application of on-line PD monitoring techniques to three phase high voltage cable joints. A simple model, using 66kV cable sections to represent a cross-bonded circuit has been implemented. The model uses one capacitive coupler per phase. Measurement data was obtained by injecting pulses into the core conductor. Data was analysed using a clustering technique in order to determine the PD source location.

Text
F2-6.pdf - Other
Restricted to Registered users only
Download (679kB)
Request a copy

More information

Published date: 2007
Additional Information: Event Dates: 8 - 13 July 2007
Venue - Dates: 9th IEEE International Conference on Solid Dielectrics, Winchester, Winchester, United Kingdom, 2007-07-08 - 2007-07-13
Organisations: Electronics & Computer Science, EEE

Identifiers

Local EPrints ID: 264257
URI: http://eprints.soton.ac.uk/id/eprint/264257
ISBN: 1-4244-0750-8
PURE UUID: 9be7ca18-31c0-42c0-81ee-ddd6b5c7ddcb
ORCID for P L Lewin: ORCID iD orcid.org/0000-0002-3299-2556

Catalogue record

Date deposited: 04 Jul 2007
Last modified: 15 Mar 2024 02:43

Export record

Contributors

Author: L Hao
Author: P L Lewin ORCID iD
Author: S J Dodd

Download statistics

Downloads from ePrints over the past year. Other digital versions may also be available to download e.g. from the publisher's website.

View more statistics

Atom RSS 1.0 RSS 2.0

Contact ePrints Soton: eprints@soton.ac.uk

ePrints Soton supports OAI 2.0 with a base URL of http://eprints.soton.ac.uk/cgi/oai2

This repository has been built using EPrints software, developed at the University of Southampton, but available to everyone to use.

We use cookies to ensure that we give you the best experience on our website. If you continue without changing your settings, we will assume that you are happy to receive cookies on the University of Southampton website.

×