Partial Discharge Estimation in a High Voltage Transformer Using a Multi Signal Decomposition Technique
Partial Discharge Estimation in a High Voltage Transformer Using a Multi Signal Decomposition Technique
A practical technique is introduced to determine the possible high frequency oscillations generated by a Partial Discharge (PD) source within a high voltage transformer. The approximation of the discharge signal is difficult to achieve because of the fixed distribution components that are present as well as non-stationary components. To solve this, a Hilbert Huang Transform is introduced to eliminate the presence of any non-stationary offset levels by employing a multi signal decomposition technique. The discharge signal is decomposed into different signal levels, and a least-square estimation technique is used to determine the harmonic decay equation parameters, that consist of signal gain, harmonic frequency, damping factor and harmonic order. The estimated parameters are then used to reconstruct the possible original partial discharge signal oscillation using only the harmonic decay equation. Knowledge of the original discharge signal allows evaluation of the severity of the PD event and may assist in condition based maintenance of the transformer.
425-428
Mohamed, R
541bddba-9997-4f3f-a82a-3e055c173974
Lewin, P L
78b4fc49-1cb3-4db9-ba90-3ae70c0f639e
Chen, G
3de45a9c-6c9a-4bcb-90c3-d7e26be21819
19 June 2009
Mohamed, R
541bddba-9997-4f3f-a82a-3e055c173974
Lewin, P L
78b4fc49-1cb3-4db9-ba90-3ae70c0f639e
Chen, G
3de45a9c-6c9a-4bcb-90c3-d7e26be21819
Mohamed, R, Lewin, P L and Chen, G
(2009)
Partial Discharge Estimation in a High Voltage Transformer Using a Multi Signal Decomposition Technique.
The 9th International Conference on Properties and Applications of Dielectric Materials, Harbin, China.
19 - 23 Jul 2009.
.
Record type:
Conference or Workshop Item
(Other)
Abstract
A practical technique is introduced to determine the possible high frequency oscillations generated by a Partial Discharge (PD) source within a high voltage transformer. The approximation of the discharge signal is difficult to achieve because of the fixed distribution components that are present as well as non-stationary components. To solve this, a Hilbert Huang Transform is introduced to eliminate the presence of any non-stationary offset levels by employing a multi signal decomposition technique. The discharge signal is decomposed into different signal levels, and a least-square estimation technique is used to determine the harmonic decay equation parameters, that consist of signal gain, harmonic frequency, damping factor and harmonic order. The estimated parameters are then used to reconstruct the possible original partial discharge signal oscillation using only the harmonic decay equation. Knowledge of the original discharge signal allows evaluation of the severity of the PD event and may assist in condition based maintenance of the transformer.
Text
ICPADM_E-06.pdf
- Version of Record
Restricted to Registered users only
Request a copy
More information
Published date: 19 June 2009
Additional Information:
Event Dates: 19 - 23 July 2009
Venue - Dates:
The 9th International Conference on Properties and Applications of Dielectric Materials, Harbin, China, 2009-07-19 - 2009-07-23
Organisations:
Electronics & Computer Science, EEE
Identifiers
Local EPrints ID: 267725
URI: http://eprints.soton.ac.uk/id/eprint/267725
PURE UUID: 86f5a747-c629-4b78-9730-9eaeca9f939f
Catalogue record
Date deposited: 29 Jul 2009 14:38
Last modified: 15 Mar 2024 02:43
Export record
Contributors
Author:
R Mohamed
Author:
P L Lewin
Author:
G Chen
Download statistics
Downloads from ePrints over the past year. Other digital versions may also be available to download e.g. from the publisher's website.
View more statistics