For some mass-impregnated (MI) paper insulated HVDC cables, unacceptably high pressures or pressure drops occur at the insulation-sheath interface under rapid loading changes, due to a strong impregnant thermal expansion or contraction. As this can degrade cables by either causing sheath plastic deformations or introducing voids into the insulation, it is important to investigate/model this thermo-mechanical phenomenon. Based on the theory of elasticity, this paper presents an analytical calculation of interfacial pressures as a function of the cable loading. Results obtained will benefit both cable operators and manufactures by provide guidelines of rating calculations and insulation designs, following a thermo-mechanical constraint.
Huang, Z Y
d9ec7ad6-0803-411d-81c5-3969f419fd44
Pilgrim, J A
4b4f7933-1cd8-474f-bf69-39cefc376ab7
19 November 2013
Huang, Z Y
d9ec7ad6-0803-411d-81c5-3969f419fd44
Pilgrim, J A
4b4f7933-1cd8-474f-bf69-39cefc376ab7
Huang, Z Y and Pilgrim, J A
(2013)
Thermomechanical Pressure Analysis for HVDC Cables.
Jicable HVDC 13, Perpignan, France.
Record type:
Conference or Workshop Item
(Poster)
Abstract
For some mass-impregnated (MI) paper insulated HVDC cables, unacceptably high pressures or pressure drops occur at the insulation-sheath interface under rapid loading changes, due to a strong impregnant thermal expansion or contraction. As this can degrade cables by either causing sheath plastic deformations or introducing voids into the insulation, it is important to investigate/model this thermo-mechanical phenomenon. Based on the theory of elasticity, this paper presents an analytical calculation of interfacial pressures as a function of the cable loading. Results obtained will benefit both cable operators and manufactures by provide guidelines of rating calculations and insulation designs, following a thermo-mechanical constraint.
Text
UtaJicable13final.pdf
- Accepted Manuscript
Restricted to Registered users only
Request a copy
More information
Published date: 19 November 2013
Venue - Dates:
Jicable HVDC 13, Perpignan, France, 2013-11-19
Organisations:
EEE
Identifiers
Local EPrints ID: 361979
URI: http://eprints.soton.ac.uk/id/eprint/361979
PURE UUID: 08a273c1-9e7b-4837-8a85-eb6550aad202
Catalogue record
Date deposited: 06 Feb 2014 20:45
Last modified: 15 Mar 2024 03:25
Export record
Contributors
Author:
Z Y Huang
Author:
J A Pilgrim
Download statistics
Downloads from ePrints over the past year. Other digital versions may also be available to download e.g. from the publisher's website.
View more statistics