Fast repetitive control with harmonic correction loops for shunt active power filter applied in weak grid
Fast repetitive control with harmonic correction loops for shunt active power filter applied in weak grid
This paper proposes a fast repetitive control (FRC) scheme with harmonic correction loops for the three-phase three-wire shunt active power filter (APF) applied in weak power grid. The FRC scheme consists of a repetitive control loop which is designed in the synchronous rotational frame and a fractional delay (FD) filter for approximating the FD caused by the fixed sampling rate. It can significantly improve the dynamic performance for the harmonic compensation. In weak grid situation, the grid frequency, voltage and then harmonic currents would vary rapidly with disturbances. A cumulative error cancellation loop is introduced into the FRC to improve the harmonic detection accuracy when grid frequency drifts. The harmonic correction loops are proposed to correct the harmonic references with selected orders when they vary rapidly with the grid voltage. With such loops, the compensation precision of the shunt APF can be highly improved. Simulation and experiment results verified the effectiveness of the proposed scheme.
Fast repetitive control (FRC), harmonic correction loop, shunt active power filter (APF), weak grid
3198-3206
Geng, Hua
4de0000a-a809-4b66-81bb-ea0befdad671
Zheng, Zedong
e9d4917b-d4f8-4836-a454-bb1c43346d08
Zou, Tianming
0f6cdc82-0054-4639-893e-4a76c859eba7
Chu, Bing
555a86a5-0198-4242-8525-3492349d4f0f
Chandra, Ambrish
c682ecf1-19d9-4cf7-afd5-ca77618ba771
1 May 2019
Geng, Hua
4de0000a-a809-4b66-81bb-ea0befdad671
Zheng, Zedong
e9d4917b-d4f8-4836-a454-bb1c43346d08
Zou, Tianming
0f6cdc82-0054-4639-893e-4a76c859eba7
Chu, Bing
555a86a5-0198-4242-8525-3492349d4f0f
Chandra, Ambrish
c682ecf1-19d9-4cf7-afd5-ca77618ba771
Geng, Hua, Zheng, Zedong, Zou, Tianming, Chu, Bing and Chandra, Ambrish
(2019)
Fast repetitive control with harmonic correction loops for shunt active power filter applied in weak grid.
IEEE Transactions on Industry Applications, 55 (3), , [8626158].
(doi:10.1109/TIA.2019.2895570).
Abstract
This paper proposes a fast repetitive control (FRC) scheme with harmonic correction loops for the three-phase three-wire shunt active power filter (APF) applied in weak power grid. The FRC scheme consists of a repetitive control loop which is designed in the synchronous rotational frame and a fractional delay (FD) filter for approximating the FD caused by the fixed sampling rate. It can significantly improve the dynamic performance for the harmonic compensation. In weak grid situation, the grid frequency, voltage and then harmonic currents would vary rapidly with disturbances. A cumulative error cancellation loop is introduced into the FRC to improve the harmonic detection accuracy when grid frequency drifts. The harmonic correction loops are proposed to correct the harmonic references with selected orders when they vary rapidly with the grid voltage. With such loops, the compensation precision of the shunt APF can be highly improved. Simulation and experiment results verified the effectiveness of the proposed scheme.
This record has no associated files available for download.
More information
Accepted/In Press date: 17 January 2019
e-pub ahead of print date: 25 January 2019
Published date: 1 May 2019
Keywords:
Fast repetitive control (FRC), harmonic correction loop, shunt active power filter (APF), weak grid
Identifiers
Local EPrints ID: 430719
URI: http://eprints.soton.ac.uk/id/eprint/430719
ISSN: 0093-9994
PURE UUID: 1ffb4f14-e2ea-4739-becc-168cc9e85a73
Catalogue record
Date deposited: 09 May 2019 16:30
Last modified: 18 Mar 2024 03:21
Export record
Altmetrics
Contributors
Author:
Hua Geng
Author:
Zedong Zheng
Author:
Tianming Zou
Author:
Bing Chu
Author:
Ambrish Chandra
Download statistics
Downloads from ePrints over the past year. Other digital versions may also be available to download e.g. from the publisher's website.
View more statistics