Bridging in contaminated transformer oil under DC and AC electric field
Bridging in contaminated transformer oil under DC and AC electric field
One of the key components in high voltage transmission and distribution systems are power transformers and their consistent operation is of utmost importance to energy utilities and users. However, transformer failures in the systems have gathered pace as more transformers are approaching or exceeding their designed lifetime. Almost 30% of total transformer failures are caused by insulation/oil contamination which has been revealed by recent analysis. Therefore, it is essential to understand the failure mechanisms/processes so the proper measures can be taken to prevent failure.
During the operation it contacts with metal, iron core and pressboard insulation inside a transformer. Contaminants such as metal filings or cellulosic residual can be formed in the oil, especially for transformers with aged paper insulation. During normal operation non-uniform fields are present within the transformer. These contaminants tend to move towards high field regions due to dielectrophoresis (DEP) forces and could form a bridge over a period of time. The bridge may potentially act as a conducting path between two different potentials within the transformer structure, leading to partial discharges or insulation failure.
There are two experimental set up have been established to investigate the bridging effect between two electrodes with different potentials under ac and dc voltages. This paper will explain the full details of the experimental setup and the results. These experiments carried out on different sizes of pressboard particles under three different ac and dc voltages. Several contamination levels have been investigated. Optical images of particle concentration have been recorded along with associated conduction current measurement during experiments. At higher voltages the rate of bridge formation is increased along with an associated current increase. The major differences between ac and dc bridges are the shapes of the bridge. The bridge formation rate for ac is slower than dc.
15
Mahmud, S
37e36ae1-2092-474b-b362-7d6b10af0247
Chen, G
3de45a9c-6c9a-4bcb-90c3-d7e26be21819
Golosnoy, I O
40603f91-7488-49ea-830f-24dd930573d1
Wilson, G
25fbd90e-6949-481c-9e75-0d457003c839
Jarman, P
390aafbd-393e-4e20-bace-b4416e0dd456
10 April 2013
Mahmud, S
37e36ae1-2092-474b-b362-7d6b10af0247
Chen, G
3de45a9c-6c9a-4bcb-90c3-d7e26be21819
Golosnoy, I O
40603f91-7488-49ea-830f-24dd930573d1
Wilson, G
25fbd90e-6949-481c-9e75-0d457003c839
Jarman, P
390aafbd-393e-4e20-bace-b4416e0dd456
Mahmud, S, Chen, G, Golosnoy, I O, Wilson, G and Jarman, P
(2013)
Bridging in contaminated transformer oil under DC and AC electric field.
Dielectrics 2013, Reading, United Kingdom.
10 - 12 Apr 2013.
.
Record type:
Conference or Workshop Item
(Paper)
Abstract
One of the key components in high voltage transmission and distribution systems are power transformers and their consistent operation is of utmost importance to energy utilities and users. However, transformer failures in the systems have gathered pace as more transformers are approaching or exceeding their designed lifetime. Almost 30% of total transformer failures are caused by insulation/oil contamination which has been revealed by recent analysis. Therefore, it is essential to understand the failure mechanisms/processes so the proper measures can be taken to prevent failure.
During the operation it contacts with metal, iron core and pressboard insulation inside a transformer. Contaminants such as metal filings or cellulosic residual can be formed in the oil, especially for transformers with aged paper insulation. During normal operation non-uniform fields are present within the transformer. These contaminants tend to move towards high field regions due to dielectrophoresis (DEP) forces and could form a bridge over a period of time. The bridge may potentially act as a conducting path between two different potentials within the transformer structure, leading to partial discharges or insulation failure.
There are two experimental set up have been established to investigate the bridging effect between two electrodes with different potentials under ac and dc voltages. This paper will explain the full details of the experimental setup and the results. These experiments carried out on different sizes of pressboard particles under three different ac and dc voltages. Several contamination levels have been investigated. Optical images of particle concentration have been recorded along with associated conduction current measurement during experiments. At higher voltages the rate of bridge formation is increased along with an associated current increase. The major differences between ac and dc bridges are the shapes of the bridge. The bridge formation rate for ac is slower than dc.
Text
Abstract - Shekhar.pdf
- Other
Text
Oral - Shekhar.pdf
- Other
More information
Published date: 10 April 2013
Venue - Dates:
Dielectrics 2013, Reading, United Kingdom, 2013-04-10 - 2013-04-12
Organisations:
EEE
Identifiers
Local EPrints ID: 352388
URI: http://eprints.soton.ac.uk/id/eprint/352388
PURE UUID: fe55f09f-db1d-45f7-8d62-513f5f4e4cad
Catalogue record
Date deposited: 10 May 2013 15:51
Last modified: 14 Mar 2024 13:51
Export record
Contributors
Author:
S Mahmud
Author:
G Chen
Author:
I O Golosnoy
Author:
G Wilson
Author:
P Jarman
Download statistics
Downloads from ePrints over the past year. Other digital versions may also be available to download e.g. from the publisher's website.
Loading...
View more statistics